F Series

Type F Valve


 F SERIES
FLUID TEMPERATURE
SENSING VALVES

  • F/FGAutomatic freeze protection
  • FP/FPR - Emergency shower freeze/scald protection
  • OSP - Automatic scald and over temperature protection
  • FR/FGR   - Automatic control for cooling systems
  • FDA - Scald protection ideal for wash stations

F Series combine excellent freeze protection and fluid temperature control with amazing economy. You get maximum performance at a minimum price.

Each type F valve has unique design features that give it special advantages in specific applications. By matching the performance advantages of the valves to your specific requirements, you can eliminate costly freeze damage, reduce the waste and cost of seasonally opened block valves, protect personnel from accidental scalding at emergency shower and eyewash stations, provide increased efficiencies in cooling water control and satisfy other temperature-related flow requirements unique to your plant facilities.

DESIGN FEATURES

Ogontz F Series valves are fully self-contained, temperature-actuated devices that employ a precision, thermal actuator for reliable operation. Each valve type includes the following features:

  • Fail-safe--(direct acting valve opens)
  • Self-contained solid/liquid thermal actuator
  • Requires no external power or remote signal
  • In-line serviceability
  • Insensitivity to line pressure
  • High repeatability--No set point drift
  • Temperature set points from 35°F to 250°F
  • Available in line sizes from 1/2" to 2"
  • 100% factory tested
     

Typical Applications

Freeze Protection of a Condensate System
Installed on a condensate receiver, the Type F valve provides positive freeze protection by draining the condensate system when fluid temperature approaches a preset, critical temperature.

Winterization of Exposed Overhead Pipe
When the fluid temperature or air temperature around an exposed water line drops toward the freezing point, the AF valve automatically bleeds the system before the fluid can freeze or before discharge freeze-up can become a problem, due to a sudden drop in air temperature. The F valve can be used for sensing water temperature only.

Freeze and Scald Protection for an Emergency Shower
Installation of FP and FPR valves (direct and reverse acting) provides both freeze and scald protection for emergency showers ( shown ) and eye wash stations.  The FDA is designed specifically for scald protection for wash down stations.

Temperature Control on a Water-cooled Air Compressor
A reverse-acting FR valve installed on a water-cooled device maintains optimum operating temperature by controlling cooling water discharge at a preset temperature, (e.g. controlled discharge between 170°F and 180°F ).

 

2835 Terwood Road, Willow Grove, PA 19090 USA 800-523-2478 E-mail: info@ogontz.com